Blauberg Turbo 125

Inline mixed flow fans
  • Maximum airflow: 350 m3/h
  • Sound pressure level LpA at 3 m: 34 dB(A)
  • Motor type: AC
  • Control: Speed switch
  • Impeller type: Mixed-flow
  • Casing material: Plastic
  • Installation in any position
  • Cable with mains plug
Unit of measurement Turbo 125
Connected air duct size mm 125
Phases - 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 25 29
Unit current A 0.11 0.13
Maximum airflow m3/h 240 350
rotation speed at 50hz -
Sound pressure level LpA at 3 m dB(A) 29 34
Weight kg 2.15
Transported air temperature (max) °С 60
Ambient air temperature min °С 0
Ambient air temperature max °С 0
Ingress protection rating - IPX4
Ingress protection rating of the drive - IPX4
Trademark Blauberg
Model Turbo 125
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
53.6 A+ 26.6 B 11.1 E
Type of ventilation unit Unidirectional
Type of drive installed Variable speed
Type of heat recovery system None
Maximum flow rate (m3/h) 275
Electric power input (W) 29
Reference flow rate (m3/s) 0.053
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.13
Control typology Local demand control
Maximum external leakage rates (%) 2.7
Sound power level (dB(A)) 54
Declared typology RVU UVU
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
69 69 69
The annual heating saved (AHS) (kWh/a) Cold Average Warm
5536 2830 1280
Datasheet
Turbo - data sheet
1.02 Mb
Manual
Turbo - user's manual
1.71 Mb
Image
Turbo 125 - image 1
566 Kb
ØD ØD1 B H L
123 164 167 190 246