Unit of measurement | Reneo D 181 S14 | |
Connected air duct size | mm | 160 |
Phases | - | 1 |
Minimum supply voltage | V | 230 |
Maximum supply voltage | V | 230 |
Power supply frequency | Hz | 50/60 |
Rated power | W | 53 |
Unit current | A | 0.49 |
Maximum airflow | m3/h | 181 |
Sound pressure level LpA at 3 m | dB(A) | 29 |
Heat recovery efficiency, max | % | 91 |
Heat exchanger type | - | Counter flow |
Heat exchanger material | - | Polystyrene |
Weight | kg | 12 |
Extract filter | - | Coarse > 60 % |
Supply filter | - | Coarse > 60 % (G4) (option: ePM1 60 % (F7)) |
Transported air temperature (max) | °С | 45 |
Ambient air temperature min | °С | 1 |
Ambient air temperature max | °С | 40 |
Ambient air humidity max | % | 60 |
Ingress protection rating | - | IP22 |
Ingress protection rating of the drive | - | IP44 |
Trademark | Blauberg | |||||
Model | Reneo D 181 S14 | |||||
Specific energy consumption (SEC) (kWh/(m2/a)) | Cold | Average | Warm | |||
82.1 | A+ | 43.2 | A+ | 18.2 | E | |
Type of ventilation unit | Bidirectional | |||||
Type of drive installed | Variable speed | |||||
Type of heat recovery system | Recuperative | |||||
Thermal efficiency of heat recovery (%) | 87 | |||||
Maximum flow rate (m3/h) | 153 | |||||
Electric power input (W) | 53 | |||||
Reference flow rate (m3/s) | 0.03 | |||||
Reference pressure difference (Pa) | 50 | |||||
Specific power input (SPI) (W/(m3/h)) | 0.204 | |||||
Control typology | Local demand control | |||||
Maximum internal leakage rates (%) | 2.7 | |||||
Maximum external leakage rates (%) | 2.7 | |||||
Sound power level (dB(A)) | 49 | |||||
Declared typology | RVU BVU | |||||
The annual electricity consumption (AEC) (kWh/a) | Cold | Average | Warm | |||
690 | 153 | 108 | ||||
The annual heating saved (AHS) (kWh/a) | Cold | Average | Warm | |||
9060 | 4631 | 2094 |